University of California, Irvine
CBEMS 135
16.4. The system shown in Fig. P16.4 is controlled by a proportional controller. The concentration of salt in the solution leaving the tank is controlled by adding a concentrated solution through a control valve. Figure P16.4 The following data apply: 1. Concentration of concentrated salt solution C1 = 25 lb salt/ft3 solution. 2. Con
...[Show More]
16.4. The system shown in Fig. P16.4 is controlled by a proportional controller. The concentration of salt in the solution leaving the tank is controlled by adding a concentrated solution through a control valve. Figure P16.4 The following data apply: 1. Concentration of concentrated salt solution C1 = 25 lb salt/ft3 solution. 2. Controlled concentration C = 0.1 lb salt/ft3 solution. 3. Control valve: The flow through the control valve varies from 0.002 to 0.0006 cfm with a change of valve-top pressure from 3 to 15 psi. This relationship is linear. 4. Distance velocity lag: It takes 1 min for the solution leaving the tank to reach the concentration-measuring element at the end of the pipe. 5. Neglect lags in the valve. (a) Draw a block diagram of the control system. Place in each block the appropriate transfer function. Calculate all the constants and give the units. (b) Using a frequency-response diagram and the Ziegler-Nichols rules, determine the settings of the controller. (c) Using the controller settings of part (b) calculate the offset when the set point is changed by 0.02 unit of concentration. This study source was downloaded by 100000874968972 from CourseHero.com on 04-13-2024 09:24:25 GMT -05:00 https://www.coursehero.com/file/16171332/HW5-Solution/ 0.0006 0.002 0.0014 4 1.167 10 (negative gain air-to-close valve) 15 3 12 therefore the controller gain, , must be negative as well (a direct-acting controller
[Show Less]